MODEL | | JTT-10L | JTT-70II/L |
Hot water capacity | kW | 10.30 | 69.80 |
COP in Hot Water (A9/A19) Refer row 40 | | 4.44 | 4.58 |
Rise in water Temp required | °C | 40 °C |
Hot water output under recirculations | L/h | 295 Liters/Hour | 2001 Liters/Hour |
Rated outlet water Temp. | °C | 55 °C |
Max outlet water Temp. | °C | 60 °C |
Space Heating capacity water (in/out):35℃/40℃ | kW | 8.2 | 57.4 |
COP Space Heating (A15/A19) Refer row 54 | | 3.53 | 3.77 |
Space Heating capacity water (in/out):40℃/45℃ | kW | 8.2 | 57.4 |
COP Space Heating (A17/A19) Refer row 55 | | 3.53 | 3.77 |
Rated power input | Kwh | 2.32 | 15.23 |
Rated current | A | 11.10 | 28.93 |
Power supply | V/Hz/Ph | 220~240/1/50 | |
Compressor type | | Copeland Scroll |
Number of Compressors | | 1 | 2 |
Heat exchanger type | | High efficiency tube intube heat exchanger |
Throttling device | | Emerson thermal expansion valve |
Condensor Fan type | | Low noise high effciency axial type |
Condensor Fan discharging | | Vertical |
Condensor Fan quantity | | 1 | 2 |
Condensor Fan input power | W | 70 | 750 |
Condensor Fan speed | RPM | 850 | 940 |
Ambient temperature | ℃ | (-25℃~+43℃) |
Refrigerant | | R407C/R417A |
Noise in 1 meter distance | dB | 59 | 68 |
Water pipe size | inch | R1 | Rc2-1/2 |
PLC Controller | | Yes Digital LCD Controller |
Daily 2 set of programmes for On / Off | | Yes | Yes |
Compressor Low / High pressure protection | | Yes | Yes |
Compressor protection water flow switch | | Yes | Yes |
Compressor Overload Protection Switch | | Yes | Yes |
Compressor time delay protection | | Yes | Yes |
Sequential Phase & Missing Phase protection | | Yes | Yes |
Automatical defrost system | | Yes | Yes |
Water Tank temp sensor & its error detection | | Yes | Yes |
Outlet hot water temp sensor & its error detection | | Yes | Yes |
Inlet water temp sensor & its error detection | | Yes | Yes |
Ambient air temp sensor & its error detection | | Yes | Yes |
Controller Communications failure | | Yes | Yes |
PCB in the Unit | | | |
Cabinet | | GI powder coated steel / Stainless Steel @ extra cost |
Product dimensions | mm | 710/ 710/ 795 | 1990/ 980/ 2045 |
Product Net weight | kg | 107 | 552 |
Package dimensions | mm | 810/ 810/ 980 | 2090/ 1190/ 2145 |
Shipping Weight | KG | 115 | 620 |
Main quality control project list:
1. Check all parts before assembling.
2. Charge nitrogen to test leakage and pressure maintaining after welding system.
3. Vacuumize, the vacuum pressure ≤30Pa
4. Leakage detection by halogen after charge refrigerant.
5. Safety testing: High-voltage insulation test and ground resistance.
6. Operation testing, record refrigerant pressure, temp. etc.
7. Inspect inside unit’s cleanliness and appearance.
Juteng is a professional company engaged in R&D, production and sales of air source and water source heating products. We have rich experience in refrigeration and heating for many years.
We have rich experience in refrigeration and heating for over decades. In line with our goal to provide environmental and climate friendly products, Juteng keeps creating more innovative and efficient energy saving products.
By 16 years’ growth our product line covers full range:
Multifunctional air to water heat pump,
All in one domestic hot water heat pump,
Split domestic hot water heat pump,
Commercial hot water heat pump,
Swimming pool heat pump,
DC inverter air to water heat pump,
EVI air to water heat pump,
Multifunctional water source heat pump,
Water to water heat pump,
Water tank (pressure bearing and insulated) for heat pumps.